How to commission the RTE-EES

  1. Switch off the dedicated lock power supply – the door must remain unlocked while the power supply is off. Switch the power supply back on. 
  2. Push the PRESS TO EXIT button – the door must remain open for the length of time set by the access control or door entry system. 
  3. Disconnect the Panel lock trig connections. Push and hold the PRESS TO EXIT button – the door must remain open as long as the PRESS TO EXIT button is held in. Reconnect the Panel lock trig connections.
  4. With DIP switch 1 ON and DIPs 2, 3 and 4 OFF, push the PRESS TO ESCAPE button. The door must remain unlocked for 1 minute. Repeat the test for the remaining timing ranges (6, 12 and 24 minutes). 
  5. Disconnect the Circuit supply connections. Push and hold the PRESS TO ESCAPE button – the door must remain open as long as the PRESS TO ESCAPE button is held in. Re-connect the Circuit supply connections. 